Kva to Amperage Calculator

How many amps does your electrical equipment draw?

Convert kilovolt-amperes (kVA) to amperage for electrical equipment sizing, circuit protection, and load calculations.

Updated June 2026 · How this works

Example calculation — edit any field to use your own numbers

Worth knowing
How It Works
The formula, explained simply

Electric current flows like water through a pipe — the bigger the pipe (voltage), the more water (power) you can move without increasing pressure (current). When you know how much total flow you need (kVA) and the pipe size (voltage), you can calculate exactly how hard the pump works (amperage). Three-phase systems are like having three synchronized pumps working together, each carrying less load than a single pump would need.

The square root of 3 factor appears because three-phase power waves are spaced 120 degrees apart, creating a mathematical relationship that reduces the peak current any single conductor must carry. This is why a 150 kVA three-phase load at 480V draws only 180 amps, while the same power on single-phase 480V would require 312 amps — nearly double.

Electrical equipment nameplates always show apparent power (kVA) rather than real power (kW) because the current you need to supply depends on the total electrical demand, including reactive components that don't do useful work but still flow through your wires and transformers.

When To Use This
Right tool, right situation

Use this calculator when sizing electrical infrastructure for known equipment loads. Generator selection, transformer sizing, circuit breaker selection, and conductor sizing all depend on accurate current calculations. It's essential for electrical panel design and load distribution planning in commercial and industrial facilities.

The calculator works best for resistive loads and equipment with known power factors near unity. Motors, lighting ballasts, and variable frequency drives introduce reactive components that may increase actual current draw beyond these calculations. For motor loads, use the full load amperage from the motor nameplate instead.

Don't use this for precise motor starting calculations or systems with significant harmonics. Large motor starting currents can be 6-8 times running current, requiring different analysis methods. Power electronic equipment like servers, LED drivers, and inverters create harmonic distortion that increases RMS current beyond what apparent power calculations predict.

Common Mistakes
Why results sometimes look wrong

The most expensive mistake is undersizing conductors and protection equipment. Many people calculate based on real power (kW) instead of apparent power (kVA), leading to dangerous overcurrent conditions. Motors and transformers draw reactive current that doesn't show up in wattage measurements but absolutely flows through your electrical system.

Another common error is mixing line voltage with phase voltage in three-phase calculations. If your equipment nameplate says 480V three-phase, that's typically line-to-line voltage, which is correct for these calculations. Using line-to-neutral voltage (277V) would underestimate current by 1.732 times, potentially causing fires or equipment damage.

Many electricians forget that kVA ratings assume perfect conditions. Real installations have voltage drop, harmonic distortion, and unbalanced loads that increase actual current draw. The calculated amperage is the theoretical minimum — always add safety margin for circuit breaker sizing and conductor selection, especially on long wire runs or in hot environments.

The Math
Worked examples and deeper derivation

The fundamental relationship is Ohm's law extended to AC power systems. For single-phase: Current = (kVA × 1000) ÷ Voltage. For three-phase: Current = (kVA × 1000) ÷ (Voltage × √3). The 1000 factor converts kilovolt-amperes to volt-amperes, matching the voltage units.

The square root of 3 (approximately 1.732) comes from vector mathematics. Three-phase voltages form 120-degree angles, and when you calculate the total power delivered, the geometric relationship reduces the current requirement by this factor. This isn't an approximation — it's the exact mathematical relationship for balanced three-phase systems.

Power factor doesn't appear in these calculations because we're working with apparent power, not real power. If you know real power (kW) and power factor, first calculate kVA by dividing kW by power factor, then use this calculator. The current calculation must account for all the electrical flow, regardless of how much actually does useful work.

Commercial Generator Sizing
150 kVA three-phase generator at 480V
Result: 180.4 amperes. This generator can supply up to 180 amps of current to your facility. You'll need a 200A main breaker and 4/0 AWG copper conductors for the main feed. The 150 kW real power assumes unity power factor — actual usable power may be lower depending on your equipment.
Residential Transformer Load
25 kVA single-phase transformer at 240V
Result: 104.2 amperes. This transformer supplies 104 amps maximum current to the home's main panel. Requires a 125A main breaker (next standard size up) and 2 AWG copper service entrance conductors. The high current reflects single-phase delivery — three-phase would be more efficient.
Industrial Motor Starter
75 kVA three-phase load at 460V
Result: 94.2 amperes. Motor starter contactors and overload relays must be rated for at least 94 amps. Use 100A standard components with 3 AWG copper conductors. The apparent power rating includes reactive components — actual motor horsepower will be lower than 75 HP equivalent.
Expert Unlock
The thing most explanations skip

Professional electrical design requires derating factors that this calculator doesn't include. Ambient temperatures above 30°C, conduit fill beyond three conductors, and conductor bundling all reduce ampacity. The NEC provides extensive derating tables that can reduce actual conductor capacity by 50% or more in adverse conditions.

Why do three-phase and single-phase give different current values?

Why do three-phase and single-phase give different current values?
Three-phase systems deliver the same power using less current per conductor because power is distributed across three wires instead of two. The square root of 3 factor (1.732) accounts for the phase relationships between the three alternating current waves. This is why industrial facilities prefer three-phase — lower current means smaller wire sizes and reduced electrical losses.
What wire size do I actually need for this amperage?
The calculator shows minimum copper wire sizes based on ampacity tables, but your installation may need larger wire due to voltage drop, conduit fill, or ambient temperature. Runs longer than 100 feet typically require one size larger. Always verify with local electrical codes and consider hiring a licensed electrician for final sizing and installation.
Why is apparent power different from real power?
Apparent power (kVA) includes both real power that does useful work and reactive power that creates magnetic fields in motors and transformers. Real power (kW) is what actually powers your equipment. The power factor determines the ratio — resistive loads like heaters have power factor near 1.0, while motors typically run 0.8 to 0.9 power factor.

Need something this doesn't cover?

Suggest a tool — we'll build it →